TXD7-A Class-A Residual Current Circuit Breaker Leakage Protection 6-63A

Pole:
  • 2P
  • 3P
  • 4P
Current:
  • 6A
  • 10A
  • 16A
  • 20A
  • 25A
  • 32A
  • 40A
  • 50A
  • 63A
Rated Residual Operating Current:
  • 30MA
  • 300MA
Quantity:

AC Breaker & Box
Technical Data
Download

Product Description

TXD7-63 Residual Current Circuit Breakers With Overload Protector are new earth leakage Circuit Breakers MCB which have been innovated, researched and developed by the company using rich production experience and international cutting-edge technology. The earth leakage Circuit Breakers have protection function of overload, short circuit, residual leakage current action, current limiting and other functions, and with international high-tech products. Products with high operating performance are suitable for the line with AC 50/60Hz, rated voltage of single-pole and two-wire, two poles for, 230V, three poles, four poles for 400V and rated current of 63A. When the leakage current from the circuit equipment or grid exceeds the specified value, residual current operated circuit breaker can cut off trouble power quickly in a very short time to protect personal and electrical equipment. The earth leakage circuit breaker can protect overload and short-circuit of the circuit or motor, it can also be converted and started infrequently under normal circumstances. The earth leakage circuit breakers meet the standards of GB16917.1-2003 and IEC61009-1, the product obtains design the national patent certificate.

Product Parameters

ModelTXD7
Protection TypeA Type (RCBO)AC Type (RCBO)
Rated Current6A,10A,16A,25A,32A,40A,50A,63A
Rated residual operated current I△n230V / 400V AC
According to the poles and current loop2P: two-poles residual current operated circuit breaker
3P: three-poles residual current operated circuit breaker
4P: four-poles residual current operated circuit breaker
According to the characteristics of instantaneous trippingC type (5 ~ 10) In, D type (10 ~ 16) In.
Rated voltage Un (V)2-Poles for 230V; 3-Poles, 4-Poles for 400V
Rated short-circuit capacity Icn (A)6000
Rated residual making and breaking capacity 6000 I △m (A)
Rated residual non-operating current I△n; 0.5I△n

Technical Parameters

Rated Voltage
 Ue (V)
Pole (P)Frame Rated Current
Inm (A)
Rated Current
(A)
Rated Leakage
Action Current
(mA)
Rated Leakage
 Non-Operating
 Current (mA)
Rated leakage
 breaking time
 (s)
Rated short-circuit
breaking capacity Icn (A)
2302326, 10, 16,
 20, 25, 32
30, 5015 , 25≤0.16000
4003
4

Outline Dimension Drawing